Chlorine Dioxide Plants Bello Zon® CDLb

Chlorine Dioxide Plants Bello Zon® CDLb

The chlorine dioxide system Bello Zon® CDLb uses the chlorite/acid process. Up to 120 g/h chlorine-free chlorine dioxide is generated from a sodium chlorite solution using hydrochloric acid in a batch process. The innovative reactor design ensures a reliable process control and achieves an outstanding efficiency well over 90 percent.
Chlorine dioxide systems type Bello Zon®  CDLb 6 and CDLb 10 with a generation capacity up to 6 rsp. 12 g/h of chlorine dioxide are especially for the combat of legionella in smaller and mid-sized public buildings, such as hospitals, hotels or sports complexes.

This guarantees cost-effcient, environmentally-friendly operation with minimal use of chemicals.


Benefits

  • Reliable process control
  • Minimal investment costs
  • Several points of injection can be operated
  • Economical operation due to minimal use of chemicals
  • High operational safety due to intrinsically safe process control
  • No CIO2 loss due to closed gas supply
  • High degree of stabillity in the CIO2 solution

Applications

  • Prevents, Legionnaires`Disease
    - Hotels, hospitals etc.
  • Disinfection for the beverage and food industry
    - Bottle rinser, CIP, bottle washing machine
    - Fruit/ vegetable rinser
  • Horticulture
    - Irrigation water and sprinkler irrigation water
  • Cooling water and potable water treatment
  • Swimming pools
    - fFlter disinfection

Technical Data

  CDLb 6 CDLb 12 CDLb 22 CDLb 55 CDLb 120
Preparation capacity g/h 6 12 22 55 120
Solution concentration mg/l 1.000 2.000 2.000 2.000 2.000
Integrated metering pump CIO2 Beta® Beta® Beta® Delta® -
  8 8 13 30  
Back pressure 7 7 7 7  
Dimensions mm (HxWxD) 1236 x 878 x 306 1236 x 878 x 306 1236 x 878 x 306 1550 x 800 x 345 1300 x 880 x 425

 

Power supply

  • 100-230 V, 50/60 Hz


Inputs

  • 2 free configurable digital inputs for the pause functions, high metering, shock dosing, or manual metering, including collective malfunction
  • 4 digital inputs for monitoring (Warning/ empty message) from teh chemical supply
  • 1 digital input for contact water meter 0.25-20 Hz
  • 1 frequency input for water meter 10-10,000 Hz


Outputs

  • 1 operating signal relay
  • 1 alarm signal relay
  • 1 warning signal relay
  • 1 voltage output +5 V as supply voltage for a water meter with Hall sensor


Operating fluids

  • Sodium chlorite 7.5%, purity according to EN 938
  • Hydrochloric acid 259%, purity according to EN 939
  • Potable water